The combustion analyzer is an all-in-one instrument that makes combustion tuning quick and easy with readings for 0⊂2, CO, CO⊂2, combustion efficiency, temperature, and draft. Additionally, it allows users to create custom reports with comments and send them through email.
The combustion analyzer is an all-in-one instrument that makes combustion tuning quick and easy with readings for 0⊂2, CO, CO⊂2, combustion efficiency, temperature, and draft. Additionally, it allows users to create custom reports with comments and send them through email.
Combustion analysis should be performed only after combustion para-meters indicate that the appliance has reached "steady-state" operating conditions. Steady-state can be gauged by three things: the change in temperature of combustion products in the vent system; the change in the percentage of oxygen in the flue gas mix, which assists in determining if there is excess air or excess fuel in the combustion process; the change in carbon monoxide (CO) over time - CO levels will spike during the initial fire which is normal, but they should normalize to a lower output as steady-state is reached.
Exclusive Tune-Rite™ On-Demand HVAC/R Assistant
At the touch of a button, the software monitors the combustion analysis process in real-time to deliver the most accurate analysis every time; make instant troubleshooting suggestions; and provide guidance based on live data plus typical characteristics of the combustion appliance.
Tune-Rite™ software eliminates the guesswork commonly involved in determining steady-state by showing you a live graphical representation of all combustion parameters as they settle into a steady-state condition.
Features
Take your investment to the next level with the Bacharach Combustion app. The mobile app, which is available for Android and iOS devices, enables users to generate and send customizable combustion reports from their smart device. Features include:
Download the App
Measured Ranges | |
Combustion Air Temperature | -4 to 600°F (-20 to 316°C) |
Flue Gas Temperature | -4 to 1202°F (-20 to 650°C) |
Oxygen (O2) | 0.0 to 20.9% |
Carbon Monoxide (CO) | 0 to 4,000 ppm |
Draft/Differential Pressure | -40 to +40 INWC (100 mBar) |
Calculated Ranges | |
Combustion Efficiency | 0.1 to 100% |
Carbon Dioxide (CO2) | 0.1 to a fuel dependent max.value in percent |
Carbon Monoxide (air free) | 0 to 9,999 ppm |
Excess Air | 0 to 250% |
General Specifications | |
User-Selectable Fuels | Natural Gas, Oil #2, Oil #4, Oil #6, Propane, Coal, Wood, Kerosene, B5 (+ 2 custom) |
Power Supply | 4 x AA alkaline batteries (incl.), universal power adapter or USB cable |
Dimensions | 8.0 x 3.6 x 2.3" (203 x 91 x 58 mm) |
Weight | 16 oz (0.4 5kg) |
Measured Ranges | |
Combustion Air Temperature | -4 to 600°F (-20 to 316°C) |
Flue Gas Temperature | -4 to 1202°F (-20 to 650°C) |
Oxygen (O2) | 0.0 to 20.9% |
Carbon Monoxide (CO) | 0 to 4,000 ppm |
Draft/Differential Pressure | -40 to +40 INWC (100 mBar) |
Calculated Ranges | |
Combustion Efficiency | 0.1 to 100% |
Carbon Dioxide (CO2) | 0.1 to a fuel dependent max.value in percent |
Carbon Monoxide (air free) | 0 to 9,999 ppm |
Excess Air | 0 to 250% |
General Specifications | |
User-Selectable Fuels | Natural Gas, Oil #2, Oil #4, Oil #6, Propane, Coal, Wood, Kerosene, B5 (+ 2 custom) |
Power Supply | 4 x AA alkaline batteries (incl.), universal power adapter or USB cable |
Dimensions | 8.0 x 3.6 x 2.3" (203 x 91 x 58 mm) |