Ideal for building control applications, this differential pressure transmitter monitors differential pressure, air velocity, and volumetric flow in a range of 10, 15, 25, 28 inWC. In addition, this transmitter simplifies the ordering process and includes an LCD and a wall mount.
Ideal for building control applications, this differential pressure transmitter monitors differential pressure, air velocity, and volumetric flow in a range of 10, 15, 25, 28 inWC. In addition, this transmitter simplifies the ordering process and includes an LCD and a wall mount.
Offers stability and versatility derived from the original MS2 series, this differential pressure transmitter delivers the desired configuration to reduce the ordering process and product setup time. Dual voltage and milliamp output signals provide control and equipment output signal verification. Additionally, it includes a linear pressure or velocity output, the square root extraction, and expands the square root capability for calculating flow.
Features
Applications
Accuracy | ±1% FSO |
Stability | ±1% FSO/year |
Limits | Temperature: -4 to 158°F (-20 to 70°C) Pressure:Ranges 0 and 1: 3.6 psi max operation, 6 psi burst; Ranges 2, 3 and 4: 6 psi maximum operation, 6 psi burst |
Power Requirements | 10 to 36 V DC (2-wire), 17 to 36 V DC or isolated 21.6 to 33 V AC (3-wire) |
Output Signals | 4 to 20 mA (2-wire); 0 to 10 V or 0 to 5 V selectable (3-wire) |
Response Time | Instantaneous (default) or 3 seconds (selectable) |
Zero and Span Adjustments | Digital push-button |
Display | 4 digit LCD |
Process Connections | ⅛", 3⁄16", ¼", 5 mm, and 6 mm ID flexible tubing |
Enclosure Rating | NEMA 4X (IP66), UL 2043 (Plenum), UL94 V-0 |
Mounting Orientation | Pressure sensor measurement unaffected by orientation |
Dimensions | Wall mount bracket: 3.14 x 1.97 x 4.84" (79.96 x 49.89 mm x 122.75 mm) Duct mount bracket: 7.48" (190.12 mm) DIN mount bracket: 3.14 x 2.32 x 3.63" (79.96 x 58.65 x 92.08 mm) |
Weight | 0.51 lbs (230 g) |
Accuracy | ±1% FSO |
Stability | ±1% FSO/year |
Limits | Temperature: -4 to 158°F (-20 to 70°C) Pressure:Ranges 0 and 1: 3.6 psi max operation, 6 psi burst; Ranges 2, 3 and 4: 6 psi maximum operation, 6 psi burst |
Power Requirements | 10 to 36 V DC (2-wire), 17 to 36 V DC or isolated 21.6 to 33 V AC (3-wire) |
Output Signals | 4 to 20 mA (2-wire); 0 to 10 V or 0 to 5 V selectable (3-wire) |
Response Time | Instantaneous (default) or 3 seconds (selectable) |
Zero and Span Adjustments | Digital push-button |
Display | 4 digit LCD |
Process Connections | ⅛", 3⁄16", ¼", 5 mm, and 6 mm ID flexible tubing |
Enclosure Rating | NEMA 4X (IP66), UL 2043 (Plenum), UL94 V-0 |
Mounting Orientation | Pressure sensor measurement unaffected by orientation |
Dimensions | Wall mount bracket: 3.14 x 1.97 x 4.84" (79.96 x 49.89 mm x 122.75 mm) Duct mount bracket: 7.48" (190.12 mm) DIN mount bracket: 3.14 x 2.32 x 3.63" (79.96 x 58.65 x 92.08 mm) |
Weight | 0.51 lbs (230 g) |